RA Series 6KVA 10KVA IP65 Outdoor Online UPS

Features:

1.Provides a pure uninterrupted AC sine wave power supply for the outdoor communication / network equipment.

2.The use of high temperature, anti cold, salt spray, anti-corrosion, anti dust, waterproof, lightning protection design.

3.Advanced MCU micro processor control Technology, ensure long life reliability.

4.Excellent Protection against over voltage, overload, over current, overcharge and so on.

5.Strong anti-jamming capacity, Lightning, surge, short-circuit, network/fax/modem surge protection. Input L and N lines reverse wiring detection.

6.DC start function, input RFC reuses function.

Description

Model

RA6KL

RA10KL

Capacity

VA/W

6000VA/4800W

10000VA/8000W

Input

Nominal Voltage

110/115/120VAC or 200/220/230/240VAC                                    200/208/220/230/240VAC

Voltage Range

125275VAC

Power Factor

≥0.97

Frequency Range

50Hz:46~54Hz; 60Hz:56~64Hz

Output

Voltage

200/208/220/230/240(1±1%)VAC

Frequency

50/60Hz (Adjustable);
50Hz AC Mode: Follow AC Mode (AC Range 46~54Hz); Battery Mode: 50Hz (1±0.2%)

60Hz AC Mode: Follow AC Mode (AC Range 56~64Hz); Battery Mode: 60Hz (1±0.2%)

Wave Form

Pure sine wave

Power Factor

0.8

Harmonic Distortion

≤2% THD (Linear load)
≤6% THD (Non-Linear load)

Overload Capacity

Load 105% work consistant;
105%load 125% 1min;
125%load 135% 30sec;135% 0.5sec

Current Crest Ratio

3:1

Connections

Terminal block

Efficiency

Battery Mode

87%

AC Mode

88%

Battery

Type

Sealed free maintenance lead acid battery

Nominal DC voltage

192VDC

192VDC

Stansard Battery Cabinet

16*38AH

16*38AH

Backup Time (Full Load)

Depens on the capacity of internal battery bank

(24AH,38AH optional)

Charge Current (Max)

2.0A

2.0A

Charge Voltage (VDC)

219.5V±1.1%VDC

219.5V±1.1%VDC

Recharge Time

Depends on the capacity of  internal battery bank

Bypass

Automatic Transfer

On overload and UPS failure

Before UPS Power-on

YES

Transfer Time

 

0 ms(from imain to battery and vice versa); Less than 4ms from inverter to bypass and vice versa

indicators

LCD Display

UPS status, Battery capacity, loading, Fault code (LCD: I/P O/P voltagefrequency, Battery voltage)

Audible

 

Bypass, Battery mode, Battery low, Overload, Fault

Communications

Intelligent RS232 serial port

Software support Windows family software, Linux, Sun network operating system, IBM Aix, Compaq True64 SGI IRIX, FreeBSD, HP-UX and MAC 

SNMP (Optional)

Remote control UPS through SNMP management and Internet

USB (Optional)

Windows family software and Mac OS

Environmental

Operating Temperature

0~40℃

Operating Humidity

095% (No condensing)

UPS dimension

L*W*H (mm)(UPS main body)

632*482*133.4

632*482*133.4

L*W*H (mm)(Cabinet)

718*595*1371

718*595*1371

Weight(kg)

Net Weight (No battery)

Make an inquiry