Features:
1.Provides a pure uninterrupted AC sine wave power supply for the outdoor communication / network equipment.
2.The use of high temperature, anti cold, salt spray, anti-corrosion, anti dust, waterproof, lightning protection design.
3.Advanced MCU micro processor control Technology, ensure long life reliability.
4.Excellent Protection against over voltage, overload, over current, overcharge and so on.
5.Strong anti-jamming capacity, Lightning, surge, short-circuit, network/fax/modem surge protection. Input L and N lines reverse wiring detection.
6.DC start function, input RFC reuses function.
Model |
RA6KL |
RA10KL |
|
Capacity |
VA/W |
6000VA/4800W |
10000VA/8000W |
Input |
Nominal Voltage |
110/115/120VAC or 200/220/230/240VAC 200/208/220/230/240VAC |
|
Voltage Range |
125~275VAC |
||
Power Factor |
≥0.97 |
||
Frequency Range |
50Hz:46~54Hz; 60Hz:56~64Hz |
||
Output |
Voltage |
200/208/220/230/240(1±1%)VAC |
|
Frequency |
50/60Hz (Adjustable); 60Hz AC Mode: Follow AC Mode (AC Range 56~64Hz); Battery Mode: 60Hz (1±0.2%) |
||
Wave Form |
Pure sine wave |
||
Power Factor |
0.8 |
||
Harmonic Distortion |
≤2% THD (Linear load) |
||
Overload Capacity |
Load <105% work consistant; |
||
Current Crest Ratio |
3:1 |
||
Connections |
Terminal block |
||
Efficiency |
Battery Mode |
87% |
|
AC Mode |
88% |
||
Battery |
Type |
Sealed free maintenance lead acid battery |
|
Nominal DC voltage |
192VDC |
192VDC |
|
Stansard Battery Cabinet |
16*38AH |
16*38AH |
|
Backup Time (Full Load) |
Depens on the capacity of internal battery bank (24AH,38AH optional) |
||
Charge Current (Max) |
2.0A |
2.0A |
|
Charge Voltage (VDC) |
219.5V±1.1%VDC |
219.5V±1.1%VDC |
|
Recharge Time |
Depends on the capacity of internal battery bank |
||
Bypass |
Automatic Transfer |
On overload and UPS failure |
|
Before UPS Power-on |
YES |
||
Transfer Time |
|
0 ms(from imain to battery and vice versa); Less than 4ms from inverter to bypass and vice versa |
|
indicators |
LCD Display |
UPS status, Battery capacity, loading, Fault code (LCD: I/P &O/P voltage&frequency, Battery voltage) |
|
Audible |
|
Bypass, Battery mode, Battery low, Overload, Fault |
|
Communications |
Intelligent RS232 serial port |
Software support Windows family software, Linux, Sun network operating system, IBM Aix, Compaq True64 SGI IRIX, FreeBSD, HP-UX and MAC |
|
SNMP (Optional) |
Remote control UPS through SNMP management and Internet |
||
USB (Optional) |
Windows family software and Mac OS |
||
Environmental |
Operating Temperature |
0~40℃ |
|
Operating Humidity |
0~95% (No condensing) |
||
UPS dimension |
L*W*H (mm)(UPS main body) |
632*482*133.4 |
632*482*133.4 |
L*W*H (mm)(Cabinet) |
718*595*1371 |
718*595*1371 |
|
Weight(kg) |
Net Weight (No battery) |