RM1-3KVA Rack mout high frequency Online UPS
Application
RM series 1KVA 2KVA 3KVA 220V Rack mount online UPS is specially designed for servers, data-center critical network devices, sensitive electronic equipment, telecom, bank, hospital, bureau, traffic, public security, ATM and so on.
Features:
Rack Mount high frequency on-line double conversion technology
DSP (Digital signal processors) control technology
Active power factor correction (APFC), input power factor up to 0.99
Output power factor 0.9
Wide input voltage range (110 V ~ 300 Vac) and frequency range (40 ~ 70 Hz)
Auto sensing frequency
50 / 60Hz frequency conversion
Cold start
Rear ventilation design and variable speed fan
Effective software and hardware protection
Quick and stable charging, 90% capacity restored in 4 h (standard model UPS)
Linear derating in low voltage input reducing battery discharging times
Settable delayed start when power is restored
Hot-swappable battery
Advanced battery management (ABM)
Multiple functions settable via LCD: output voltage, EOD, auto-start, bypass mode, ECO mode and frequency conversion mode
Multi-platform communications: RS232 (standard), USB / RS485 / SNMP / dry contacts (optional)
Description

Model

RM1K-C

RM1KL-C

RM2K-C

RM2KL-C

RM3K-C

RM3KL-C

Rated Power

VA/W

1KVA/800W

1KVA/800W

2KVA/1600W

2KVA/1600W

3KVA/2400W

3KVA/2400W

Input

Phase

Single Phase with Ground

Nominal Voltage

110/115/120Vac or 220/230/240Vac

Voltage Range

60-138VAC  or 115 ~ 300VAC

Frequency Range

46 ~ 54Hz(default), user adjustable within 40~60Hz

Power Factor

0.97

Connection

IEC320-10A inlet

IEC320-16A inlet

Output

Phase

Single Phase

Voltage

110/115/120Vac or 220/230/240VAC ± 2%

Frequency

46~54Hz or 50Hz ± 0.2Hz (Line mode)

50Hz ± 0.2Hz ( Battery mode)

Waveform

Pure Sine Wave

Overload Capability

108%~150% for 30 sec., 150% for 300 ms

Current Crest Ratio

3:01

Connections

IEC320-10A *4

IEC320-10A*4 

IEC320-10A*4

IEC320-10A*4

IEC320-10A and Terminal Block

IEC320-10A and Terminal Block

Bypass

Automatic Transfer

on overload and UPS failure

Before UPS Power-on

Default “NO”, user adjustable to “YES”

Voltage Range 

80~264VAC (Default), user adjustable within 80~286VAC

Transfer Time

0 ms; less than 4 ms from inverter to bypass and vice versa

LED indicators

Load level / Battery level, Battery , Utility Power, Inverter, Bypass, Overload, Fault

Audible Alarm

Bypass, On battery mode, Battery low, Overload, Fault

Communications

RS-232 Serial Interface

Intelligent Slot;

OPTIONS:  WEBPOWER SNMP/WEB card, AS400 card or WinPower CMC)

Network Surge Protection

RJ45 I/O port available for network or Fax/Modem

Environmental

Operating Temperature

0 ~ 40°C

Operating Humidity

20 ~ 90% non-condensing

Main Unit

Net Weight (Kg)

13.90 

7.50 

28.50(3U)
8.50(2U)

8.90 

29.60(3U)
10.00(2U)

10.50 

Dimensions

(LxWxH) mm

483*467* 88

(2U)

483*467*88 (2U)

484*634*134

(3U internal batteries)

483*467*88

(2U)

483* 467*88 (2U)

484*634*134

(3U internal batteries)

483* 467*88

(2U)

Battery Pack

Type

Internal Batteries

External Battery Pack

External Battery Pack